Vacuum Chamber ZKTJ-160/1.14
Vacuum Chamber ZKTJ-160/1.14
Parameter
No. |
MAIN TECHNICAL DATA |
Unit |
|
|
1 |
Rated Voltage |
kV |
1.14 |
|
2 |
Lightning Impulse Withstand Voltage (Peak) |
kV |
|
|
3 |
Short-time (1min) Power-frequency Withstand Voltage |
kV |
6 |
|
4 |
Rated Frequency |
Hz |
50/60 |
|
5 |
Rated Current |
A |
160 |
|
6 |
Rated Short-time Withstand Current |
kA |
|
|
7 |
Rated duration of Short-circuit |
s |
1 |
|
8 |
Rated Breaking Current |
A |
1600 |
|
9 |
Limiting Breaking Current |
kA |
2 |
|
10 |
Rated Making Current |
kA |
1.92 |
|
11 |
Rated Operating Frequency |
AC-3 |
Operations/h |
600 |
AC-4 |
150 |
|||
12 |
Short-time Operating Frequency |
Operations/h |
3000 |
|
13 |
Utilization Category |
AC |
|
|
14 |
Electrical Endurance |
AC-3 |
Operations |
3*106 |
AC-4 |
6*104 |
|||
15 |
Mechanical Endurance |
Operations |
10*106 |
|
16 |
Clearance Between Open Contacts |
mm |
1.5~2 |
|
17 |
Contact Closing Force Due to Bellows and Atmosphere |
N |
20+ -10 |
|
18 |
Counter force of Contacts at Full Stroke |
N |
32+ -10 |
|
19 |
Circuit Resistance at Min. Rated Contact Force |
μΩ |
|
|
20 |
Contact Limit Erosion |
mm |
1 |
|
21 |
Mass of Moving Parts |
kg |
0.06 |
|
22 |
Internal Gas Pressure |
Pa |
<=1.33*10-3 |
|
23 |
Shelf Life |
Year |
10 |